Gamewell-FCI

Gamewell-FCI ASD-PL3R Velociti Addressable Smoke Detector

$73.50
$73.50
Shipping calculated at checkout.

Free 30-Day Returns

42 in stock

The Gamewell-FCI ASD-PL3R is the remote-test variant of the Velociti Series 3 photoelectric detector. It shares the re-engineered UL 268 7th Edition optical chamber and Velociti loop integration of the ASD-PL3, with the added ability to be tested remotely when installed in a duct housing.

Each detector occupies one address on a Gamewell-FCI Velociti loop and reports continuous temperature data back to the panel. Rotary decimal switches set addresses from 01 to 159. Dual bicolor LEDs provide 360 degree visibility (green on poll, red on alarm).

Remote test capability for duct installations

The R in ASD-PL3R stands for remote test. When the detector head sits inside a duct housing on a return-air or supply-air duct, physical access for routine functional testing becomes impractical. The ASD-PL3R accepts a test signal from a remote test station so testing can happen at floor level instead of at the duct.

Use with DNR or DNRW duct housing

The ASD-PL3R is the detector head only. Pair it with the Gamewell-FCI DNR (non-relay) or DNRW (non-relay, watertight) duct housing for return-air or supply-air duct monitoring per NFPA 90A and IMC 606. Without the duct housing the remote-test capability has no application, for non-duct installs, use the standard ASD-PL3 instead.

Compatible panels: E3 Series, S3 Series, GWF-7075

ASD-PL3R runs on Velociti protocol. E3 Series and S3 Series panels speak Velociti natively with full feature support. GWF-7075 supports Velociti but not CLIP, relevant only when mixing this loop with -IV detectors.

Listings and approvals

UL Listed S2332 under UL 268 7th Edition. FM Approved 3023594. CSFM 7272-1703:0501. MEA FDNY COA-219-02-E Vol. VI. ISO 9001 certified manufacturing.

Operating environment expanded for duct

When installed inside a DNR/DNRW duct housing, the operating temperature range expands from the standard 32-122°F up to -4°F to 158°F (-20°C to 70°C). Air velocity tolerance: 0 to 4,000 ft/min. Humidity: 10-93% non-condensing.

Payment method

  • American Express
  • Apple Pay
  • Diners Club
  • Discover
  • Google Pay
  • Mastercard
  • PayPal
  • Shop Pay
  • Visa

Free delivery on orders over $100 to US Continental

Free 30-day returns

View full details

Specifications

Voltage Range
15 to 32 VDC
Standby Current
200 µA @ 24 VDC (1 comm every 5 sec, green LED enabled)
Alarm Current
2 mA @ 24 VDC (red LED enabled)
Operating Temperature
32°F to 122°F standard; -4°F to 158°F in DNR/DNRW duct housing
Humidity Range
10% to 93% non-condensing
Velocity Range
0 to 4,000 ft/min (0 to 1,219.2 m/min)
Dimensions
2.0 in (51 mm) installed in B300-6 base
Weight
3.4 oz (96.4 g)
Available Colors
white

Compatibility

Protocol family: Velociti

Supported protocols

  • Velociti

Control Panels

Liquid error (sections/fa-product-specs line 134): Could not find asset snippets/fa-compat-card.liquidLiquid error (sections/fa-product-specs line 134): Could not find asset snippets/fa-compat-card.liquidLiquid error (sections/fa-product-specs line 134): Could not find asset snippets/fa-compat-card.liquid

Certifications & Compliance

  • UL Standard: UL 268 (7th Edition)
  • UL Listing: S2332
  • FM Approved: 3023594
  • MEA FDNY: COA-219-02-E Vol. VI
  • CSFM: 7272-1703:0501
  • ISO 9001 Certified